TROUBLESHOOTING
64
HYDRO-VIEW USER GUIDE
D0022
REV 1.06
Troubleshooting
Factory test display
The Hydro-View includes a factory test display page to assist in troubleshooting if
problems are suspected with the Hydro-View itself. This requires a special access code -
see
Access codes
(p79) and once selected, it is necessary to remove power from the
Hydro-View to restore normal operation.
Since this function exercises the inputs and outputs of the Hydro-View, it is not
recommended that this be used when the Hydro-View is connected to the plant. The test
page performs the following operations…
Displays the voltage at the sensor input.
Cycles the voltage/current on the analogue output between 0, 50% and full scale.
Operates each output relay in turn.
Performs an external loop-back test on the serial port. You must connect transmit
data to receive data to see this.
Displays the state of the digital inputs.
To use the factory test display...
1. Remove power to the Hydro View.
2. Disconnect all wires connected the Hydro View terminals after first noting their
positions.
3. Connect jumpers in the positions shown in Figure 29. If you wish to test the RS232
port, you will need to use a RJ11 to 9-pin D-type connecting cable, available from
Hydronix.
4. Re-apply power and enter pass code given in
Access codes
(p79).
5. Select menu option Factory Test.
If the Hydro-View is working correctly the following actions will take place on the display...
Analogue output voltage (OUT) will cycle between 0, 5 and 10V.
Sensor input voltage (IN) will cycle between 0, 5 and 10V at the same time as the
output voltage due to the feedback wiring.
Output relays (out) 1, 2 and 3 will cycle in a binary sequence...
3
2
1
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
0 0 0
etc.
Digital input signals (in) 1 and 2 are connected back to relays 1 and 2 and will
therefore follow the pattern above.
Battery (Batt) will display 1 if the internal Lithium battery is healthy, otherwise it will
display 0.
Содержание Hydro-View HV02
Страница 20: ...20 HYDRO VIEW USER GUIDE D0022 REV 1 06 Notes ...
Страница 30: ...MATERIAL IN USE 30 HYDRO VIEW USER GUIDE D0022 REV 1 06 Notes ...
Страница 42: ...SUGGESTED WORKING VALUES 42 HYDRO VIEW USER GUIDE D0022 REV 1 06 Notes ...
Страница 48: ......
Страница 53: ...GROUPING CHANNELS HYDRO VIEW USER GUIDE D0022 REV 1 06 53 Figure 17 Four bin grouped system ...
Страница 54: ...EXAMPLE A FOUR BIN GROUPED SYSTEM USING RS485 54 HYDRO VIEW USER GUIDE D0022 REV 1 06 Notes ...
Страница 69: ...INSTALLATION HYDRO VIEW USER GUIDE D0022 REV 1 06 69 Notes ...
Страница 70: ......
Страница 80: ...ELECTROMAGNETIC COMPATIBILITY DIRECTIVE 89 336 EEC 80 HYDRO VIEW USER GUIDE D0022 REV 1 06 Notes ...
Страница 82: ...82 HYDRO VIEW USER GUIDE D0022 REV 1 06 Notes ...