TransformerCare Unit
TCU components
HYDAC FILTER SYSTEMS GMBH
en
Page 16 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05
Item
Designation
1
Electrical switch box. Depending on the type, not installed on the console
and must be installed outside the cover. Units built after 08/2010 must
always be installed separately and externally.
2
Motor-pump assembly
3
Patented dewatering and degasification unit
4
Clogging indicator
5
Fluid filter
6
Electronic pressure switch (EDS) for monitoring the pressure (vacuum) in
the dewatering and degasification unit, and thus indirectly the total content
in the insulating oil.
7
Pressure control valve to build up the required pressure for the
degasification and dewatering unit (20 bar)
8
Bleed screw for dewatering and degasification unit
9
Automatic shut-off valve
10
Measurement point upstream of the fluid filter for taking oil samples, e.g. for
DGA
14
Safety switch reports leaks and full safety drip tray reports problems and
deactivates the TCU
17
Filter unit bleed screw
18
Measurement point in front of the differential pressure relief valve
20
Drip tray
21
Main switch
22
AquaSensor AS 1000 (optional) for continuous measurement of the water
saturation level (relative moisture) as a percentage.
23
Gas withdrawal connection for taking gas samples. A small quantity of
insulating oil required to lubricate and seal the internal vacuum pump is
ejected here.