TransformerCare Unit
TCU Dimensions / Drilling Template
If the TCU stops because of the safety switch (14) or the float switch in the optional
collecting canister, the TCU will restart automatically once the switch has been
disengaged, provided the stopping pressure (SP1) was not reached during the idle
period as a result of the pressure balance.
When the TCU starts without the electronic pressure switch EDS (6) displaying
anything and it stops after the delay time has expired, the fuse (F1) in the control
circuit was probably tripped and needs to be reset.
The signal lamps (H1) on the switch box light up if the alarm pressure (SP2) is
exceeded. When the alarm pressure (SP2) is reached, relay K2 switches.
The motor circuit breaker (Q2) protects the motor against electric overload if the
pump fails or short circuits.
TCU Dimensions / Drilling Template
The following diagram shows the TCT with a cover hood. The hood is equipped with
a hinge.
The TCU retaining frame has 4x Ø 10 mm mounting holes.
The distance between the bore holes is 710 mm horizontally and 600 mm vertically.
HYDAC FILTER SYSTEMS GMBH
en
Page 21 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05