TransformerCare Unit
Technical Data
HYDAC FILTER SYSTEMS GMBH
en
Page 62 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05
Technical Data
Weight (empty)
~ 70 kg, including weather hood
Dimensions (L x W x H)
785 x 750 x 395 mm
Electrical Installation
See type label
Power consumption
~ 550 W
Hydraulic connection
Inlet: G3/4”
Outlet: G3/8”
Flow rate (50Hz)
For continuous operation 15 m³ per week
Filtration rating
3 µm absolute
Permitted pressure at the TCU
suction connection
0,1 … 0,5bar
Storage temperature range
-20 … 40 °C
Ambient temperature range
-35 … 50 °C
Fluid temperature
90 °C maximum
Viscosity range
5 … 300 mm²/s
IP class
IP55