TransformerCare Unit
Electrical connection of the TCU
Electrical connection of the TCU
DANGER
Electric shock
Danger of fatal injury
►
Any work involving electrical equipment may only
be done by a properly trained, certified electrician.
NOTICE
Incorrect rotation direction of the motor
The TCU/the electronic pressure switch is damaged.
►
Check the rotation direction of the motor after installation.
Connect the TCU to the power supply. Observe the voltage specifications on the
type label of the TCU / the electric motor.
Depending on the design, the TCU is supplied with or without a power plug.
See the enclosed circuit diagram for the electrical connections.
In 3-phase operation: Using jog mode (quick switching on and off), check the
rotation direction of the electric motor.
An arrow on the housing shows the correct direction of rotation.
If it is necessary to change the direction of rotation, change two phases in the
connection housing of the electrical motor.
HYDAC FILTER SYSTEMS GMBH
en
Page 27 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05