TransformerCare Unit
Installing the TCU
HYDAC FILTER SYSTEMS GMBH
en
Page 24 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05
The typical density (D) is:
Mineral oil
0.88
kg / dm³
Silicon oil
0.96
kg / dm³
Midel 7131
0.97
kg / dm³
Please note that additional threaded connections, bends or constrictions increase
the pressure difference.
Connecting the suction line
Proceed as follows to connect the suction line:
1.
Connect the suction hose (15) to the upper connection (shut-off fitting) on
the transformer (20).
2.
Fit the manual ball valve included to the free end of the suction line and
close it.
Do not connect the suction hose to the TCU yet.
Connecting the return line
Proceed as follows to connect the return line:
1.
Fit a check valve with 1 bar opening pressure to the lower connection
(shut-off fitting) of the transformer. The check valve prevents the
transformer draining via this connection.
When fitting the check valve, ensure that the direction of flow is correct.
Return flow from the TCU to the transformer must be guaranteed.
2.
Connect the return hose (16), with the G3/8” adapter to the lower outlet
(OUT) of the TCU.
Do not connect the return hose to the transformer yet.