TransformerCare Unit
Draining and decommissioning the TCU
Draining and decommissioning the TCU
To decommission, proceed as follows:
1.
When the oil level in the degasification and
dewatering unit reaches ~ ½ fill level, close
the ball valve (5) at the inlet of the TCU.
2.
Switch the TCU off at the main switch.
3.
Open the bleed plug in the cover of the filter
housing. The oil is sucked from the filter
housing into the degasification unit.
4.
Loosen the measuring hose at the front on
the block of the degasification and
dewatering unit.
5.
Hold a suitable vessel with a capacity of at
least 2 liters under the connection and
remove the measuring hose.
6.
The degasification and dewatering unit is
still under vacuum pressure, which is why
only a little oil drips from the connection
nozzle in the block.
7.
Open the bleed nozzle in the head of the
degasification and dewatering unit.
8.
The oil now flows out of the degasification
and dewatering unit.
9.
Unscrew the 4 screws on the filter housing
cover counter-clockwise.
HYDAC FILTER SYSTEMS GMBH
en
Page 59 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05