Poseidon2
– Family manual
HW group
www.HW-group.com
14 / 104
Sensors
After connecting sensors or changing RJ11 connections, sensors need to be detected again.
NOTE:
Configuration changes must be confirmed by clicking the Apply Changes button.
Sensor name will be shown
in e-mails, text messages,
or SNMP traps
Sends a
SNMP trap
if the “Safe
Range” for this sensor is
exceeded
Scans connected sensors and
displays detected sensors
Sends an
if the “Safe
Range” for this sensor is
exceeded
Sends a
text message (SMS)
if
the “Safe Range” for this sensor is
exceeded
Range of allowed values. If
exceeded, alarm is signaled.
To avoid numerous false alerts
(by e-mail or SMS) whenever the reading
fluctuates around the threshold,
you can use:
1)
Hysteresis Idle Range
Tolerance band around the
“Safe Range”. Prevents
multiple alarm alerts.
2)
Delay [s]
Delays the information about
alarm beginning and alarm
end by a specified time. Can be used for dry contacts, too.
Tip:
For details, see the complete “Poseidon family” manual.