Output Control
Manual
– Output controlled over the web or M2M protocols (XML, SNMP..)
Change to On / Off
– Change output state (after confirming with Apply
Changes)
Local Condition
– Output is controlled by the sensor state condition.
For M2M protocols the output value is for reading only (output cannot be controlled)
.
Output is controlled by the Target Value, hysteresis (IDLE Range) set for the specific
sensor is used.
On if any alarm
The output is closed if at least one of the inputs or sensors is in alarm.
This condition accepts also DELAY and HYSTERESIS settings of the specific
active sensors and inputs.
On if alarm on
This output switches if an Alarm occurs on a specific selected sensor (input).
On if value equal to Trigger
The output is closed if the value matches the Target Value setting.
On if value higher than Trigger
The output is closed if the Current Value is greater than the Target Value
setting.
On if value Lower than Trigger
The output is closed if the Current Value is lower than the Target Value setting
Trigger Value
– Border value of the condition
(This output switches On for example if the value is higher than the
Trigger Value
)
Dependent On
– Selection of a sensor to which the condition applies.
Note:
Output conditions are not supported on Poseidon 2250.
Local conditions are also called
IP Thermostat mode
.