Supported interfaces (in details)
Dry Contact Inputs
Dry contacts can be connected to the clamps. For
example Door contact.
The inputs are electrically connected to the power
supply.
Unconnected inputs read as “
0 (Off)
”.
Activated inputs (closed contacts) read as
“
1 (On)
”, resistance against the Common
pin must not exceed 500Ω.
Connection parameters:
Maximum wiring length:
50 m
Supported sensors:
Any contact without external voltage (dry contact)
Per-input alarm settings:
o
Alarm inactive
o
Alarm when the contact is opened or closed
o
Alarm whenever the contact is open
Possible alarm responses:
Common setting for all inputs
o
No response
o
Alarm alert sent as a SNMP trap
o
Alarm alert sent by e-mail or text message (SMS)
o
Alarm alert sent as a SNMP trap as well as by e-mail or SMS
Polling period:
800 ms
Range of sensor IDs:
Inputs use ID addresses from 1 to 9
Sensor names:
Sensors can be named using up to 12 characters
Disconnected sensor detection:
None, disconnected sensor reads as “
O (Off)
”.