The sensors must be with Autodetection after every change.
Name
– Name of the input, up to 12 chars (e.g. “above door”, “area1 humid”).
Sensor ID
– Unique sensor identifier, specifies its address on the bus.
More about sensors addressing can be found in materials about Poseidon family.
Range for sensors is
[65..150]
and
[256..65535]
Code
– Full ID of the 1-Wire sensor
Value -
actual sensor state.
Sensors that are not found or not working read as
-999.9
.
Safe Range
Range of values which are considered to be OK.
With Safe Range set to
15,0
– 35,0
an alarm e-mail will be sent when the values are
below
14,9
and
above 35,1
.
Hysteresis
Defines a
tolerance band
when exceeding a
threshold in order to avoid raising multiple
alarms when the reading fluctuates near the
threshold.
See the detailed description in the Sensor
Hysteresis section.
Delay [s]
Delays the information about alarm beginning
and alarm end.
Out of Safe Range
Defines the response if a reading is outside of
its safe range
SNMP Trap
– Enables sending a SNMP trap upon alarm activation/deactivation
– Enables sending an e-mail upon alarm activation/deactivation
SMS
– Enables sending an SMS upon alarm activation/deactivation
Note:
SMS (text messages) are sent through a GSM modem connected directly to the
Poseidon unit via the RS-232 interface.