Outputs
Pulse Timer
–
After clicking this option the output will switch for a defined time.
Pulse Timer = 0 function inactive
Details can be found in the manual in chapters
about WEB interface.
Output mode:
A)
Manual
Output can be controlled using the Web interface or externally using M2M protocols. The
output
cannot be used in “thermostat” mode – local condition.
B)
Local Condition
The output cannot be controlled over the Web, it is controlled by the local condition. The
output is read-only for all M2M protocols. Hysteresis in the sensor settings applies.
Outputs cannot be controlled via web or M2M protocols in
Local Condition
mode.
o
On if any alarm
The output is active if at least one input or sensor is in alarm.
o
On if value equal to Trigger
The output is active if the selected sensor reading
is equal to
the “Target Value”.
o
On if value higher than Trigger
The output is active if the selected sensor reading
is greater than
the “Target Value”.
o
On if value lower than Trigger
The output is active if the selected sensor reading
is less than
the “Target Value”.
Choose the
output mode
Manual
mode:
Output controlled over the WEB
or M2M protocols
Local Condition
mode:
Controls the output according to
the specified sensor
Enter Digital Input name,
will be shown in e-mails,
text messages or SNMP
traps
Pulse output
timer [s].
Default
Pulse Timer = 0
sets
the output to a standard state.