Poseidon2
– Family manual
HW group
www.HW-group.com
87 / 104
Logger format
Logged data from the logger:
x.x.x.x/
spilog.bin
binary format of the logged data
x.x.x.x/
spilog.txt
Text format (CSV) of the logged data
x.x.x.x/
spilog.del
call this file to delete logged data and start logging again
Logger is circuit buffer = oldest data are rewrite by newer data.
spilog.txt
yyyy/mm/dd;hh:mm:ss;log_type;log_group;value_count;value_id[0];value[0];value_id[1];value[1]; ...
value_id[value_count - 1];value[value_count - 1];
log_type
0 - normal (periodical), 1 - alarm
log_group
Type of sensors
o
0 - Wire1 sensors,
o
1 - RS232 sensors,
o
2 - RS485 sensors,
o
3 - inputs,
o
4
– outputs
value_count
# of values in this record
value_id[i]
Unique ID in the Poseidon device
o
1..64
– Digital inputs,
o
128..
– Digital outputs,
o
65 ('A') .. 122 ('z') - RS485 sensors,
o
0 .. 1 - RS232 sensors,
o
256 .. 65535 - Wire1 sensors
value[i]
the most important number in this babel of digits
spilog.txt SCV file format example
2007/04/02;14:26:51;0;0;7;54896;243;28078;242;27385;243;25539;245;55499;243;14127;243;4127;246;
2007/04/02;14:26:51;0;2;2;74;245;106;359;
2007/04/02;14:26:51;0;3;3;1;0;2;0;3;0;
2007/04/02;14:26:51;0;4;2;128;0;129;0;