Calibration
Each sensor can be calibrated by specifying a linear offset. The calibration value can be
written over XML. For calibration settings use the
Calibrator utility
(For download on
Poseidon 2250 websites)
or EX104 from HWg SDK
(menu can be opened by a right-click)
.
Calibration value = +3 → sensor measures 0,5°C → Poseidon shows +3,5°C
Calibration value = -
3 → sensor measures 0,5°C → Poseidon shows -2,5°C
Calibration value = -
10 → sensor measures 27% RH → Poseidon shows 17% RH