![Huawei USG9500 Series Скачать руководство пользователя страница 481](http://html.mh-extra.com/html/huawei/usg9500-series/usg9500-series_hardware-manual_168098481.webp)
Item
Requirements
Installation
position of the
air conditioner
Install the air conditioner in a suitable location so that it does not blow air
directly onto the device.
Other
Protect the equipment room from mildew and rodents.
Figure A-74
Internal partition wall inside the equipment room
设备
空调
隔断
A.3.4 Requirements for Temperature, Humidity, and Altitude
Ensure proper temperature and humidity in the equipment room. Ensure the altitude of the
equipment room in the regulated range.
lists the temperature, humidity, and
altitude requirements for the equipment room.
Table A-33
Requirements for temperature, humidity, and altitude
Item
Requirements
Environmental
temperature
a
Long-term
operation
b
0°C to 45°C
Short-term
operation
-5°C to 50°C
Storage temperature
-40°C to 70°C
Environmental
relative
humidity
Long-term
operation
5% RH to 85% RH, no coagulation
Short-term
operation
5% RH to 95% RH, no coagulation
Storage relative humidity
0% to 95%
Long-term altitude
Less than 3,000 m
HUAWEI USG9500 Series
Hardware Guide
A Appendix
Issue 03 (2017-12-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
469