Item
Indicator
Color
Status Description
SFU
RUN
Green
From the time the SFU is powered on
until it is registered, the indicator status
changes from off, blink once every 250
ms (4 Hz), off, steady on, and then to
blink once every two seconds (0.5 Hz).
After the SFU is registered, the SFU is
working properly if the indicator blinks
at 0.5 Hz.
ACT
Green
If the indicator is steady green, the SFU
is working properly; if the indicator is
off, the SFU is faulty.
2.2.12 Powering On the USG9580 - AC Power Distribution
Check whether the USG9580 is operating properly with AC power supply. To prevent
damage, power on the USG9580 according to the instructions in this section.
Context
CAUTION
Before performing a power-on check, switch all circuit breakers to the OFF position.
Before you power on the USG9580, ensure that:
l
The power cable and PGND cable are properly connected.
l
The power switch in the equipment room is easy to locate so that you can quickly power
off devices in case of any problems.
Procedure
Step 1
Turn on external AC power supplies A and B.
Step 2
Measure the input voltage of the AC power chassis with a multimeter to ensure that the
voltage falls between 90 V AC and 264 V AC.
Step 3
Turn on the circuit breakers of external AC power supplies A and B and check the status of
the indicators on the AC power chassis.
Step 4
Measure the input voltage of the device with a multimeter to ensure that the voltage falls
between -72 V DC and -38 V DC.
Step 5
Measure the input voltage of the device with a multimeter to ensure that the voltage falls
between -72 V DC and -38 V DC.
Step 6
Wait for three minutes and then check the status of the indicators.