NOTICE
With the 110 V AC power supply, the USG9580 must use 110 V dual-live-wire AC input
to meet the maximum system power consumption with the full configuration. This is
because AC power modules are half-load output with 110 V AC input, which cannot
meet the system power consumption.
Cabinet Requirements
You are advised to use Huawei standard NE68E cabinet. Any other cabinet must meet
Requirements for Customers' Cabinets Purchased from Other Vendors
.
Cabinet Clearance Requirements
The N68E-22 cabinet is used as an example. As shown in
, cabinet clearance must
meet the following requirements:
l
Aisles in the equipment room ≥ 1000 mm; aisles between cabinet rows ≥ 1000 mm
l
Space between cabinet sides and wall ≥800 mm
l
Space between cabinet row and wall ≥ 1000 mm
Figure 2-5
Diagram for cabinet deployment
≥1000mm
800mm
00m
m
m
≥1000mm
≥800mm
600mm
600mm
600mm
m
Device Deployment Requirements
The USG9580 chassis is 32 U high and requires front and back maintenance mode. Device
deployment must meet the following airflow and maintenance clearance requirements: