Item
Specification
Note
If the PDF cannot provide 70 A circuit breakers and full configuration is unnecessary,
select the circuit breaker of each DC line using the following formula (A1,A2,B1,B2).
I = P / (Vin * D * 2)
I: rated current of the circuit breaker of each line on the PDF, in Ampere (A).
P: total power of each device.
Vin: input voltage of the power supply. (38 < Vin < 72)
D: derating coefficient. The recommended coefficient is 0.8.
2: number of the input lines of power module.
describes how to select power cables (a1,a2,b1,b2)
Table 2-16
Cables for the PEMB
Distance from the PDF to
the Device
Power Cables a and b
Shorter than or equal to 15
m
Wire,450/750V,227 IEC
02(RV)16mm
2
,blue,85A
Each power module should
be equipped with one cable
of this type. The cable
length is determined by an
onsite project survey.
Wire,450/750V,227 IEC
02(RV)16mm
2
,black,85A
Each power module should
be equipped with one cable
of this type. The cable
length is determined by an
onsite project survey.
Naked Crimping
Terminal,JG2,16mm
2
,M6,95
A,Tin Plated,for OEM
Each cable should be
equipped with one terminal
of this type.
Naked Crimping
Terminal,OT,16mm
2
,M8,Tin
Plating,Naked Ring
Terminal
Each cable should be
equipped with one terminal
of this type.
Longer than 15 m or shorter
than or equal to 25 m
Wire,450/750V,227 IEC
02(RV)25mm
2
,blue,110A
Each power module should
be equipped with one cable
of this type. The cable
length is determined by an
onsite project survey.
Wire,450/750V,227 IEC
02(RV)25mm
2
,black,110A
Each power module should
be equipped with one cable
of this type. The cable
length is determined by an
onsite project survey.