Figure 3-33 Connecting teamwork cables
Connecting Monitoring Cables
NetCol8000-A013 supports RS485 monitoring.
●
If there is no teamwork networking, connect the smart cooling products
hand-in-hand and connect the CN17 port on the first smart cooling product
to the monitoring device. An ≤ 255.
●
In teamwork networking, connect the CN17 port on the first smart cooling
product in the teamwork networking to the monitoring device. An ≤ 32.
Considering the monitoring speed, it is recommended that An be less than or
equal to 8.
Figure 3-34 Connecting RS485 monitoring cables
3.11.6 Cable Routes
The bottom routing for power cables and the signal cable between indoor and
outdoor units is shown in the figure.
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
3 Installation Guide
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
54