Figure 4-11 Charging refrigerant
(1) Electronic balance (2) Refrigerant
cylinder
(3) Pressure gauge
(4) Needle valve of
gas pipe stop valve
2. After the compressor speed stabilizes at 3000 rmp for about 10 minutes,
choose Run > Device Run State to view the Suction Pressure, Discharge
Pressure, and EEV Suct Superheat, and Supercool. Check whether the
suction pressure, discharge pressure, EEV suction superheat degree, and
supercool degree is within the reasonable range.
Table 4-7 Running parameters
Outdoor
Ambient
Temperatur
e
Normal
Discharge
Pressure
Range
Normal
Suction
Pressure
Range
Reasonable
Suction
Superheat
Degree
Supercool
Below 15°C
1.5–2.5 MPa
0.7–1.2 MPa
4–10°C
3–5°C
15–35°C
1.5–3.1 MPa
35–45°C
2.5–3.8 MPa
Above 45°C
3.1–4.15
MPa
3. On the diagnostic mode screen, change the compressor input to 0 rpm.
Step 7 Commission the humidifier.
1. Confirm that the upstream inlet valve of the wet film humidifier is open.
2. In diagnostic mode, start the wet film humidifier.
3. Check that the water inlet pipe does not leak during the process.
4. In diagnostic mode, close the wet film humidifier.
Step 8 After the commissioning is complete, remove the device used for charging the
refrigerant, and install the valve bonnet.