3.11.5 (Optional) Connect Teamwork and Monitoring Cables
Network Cable Pin Definition
Table 3-8 Port pins for teamwork and monitoring
Port
Pin
Signal Attribute
Description
CN16
Pin1
RTU-RS485-D+
Monitoring
communications
Pin2
RTU-RS485-D-
Pin3
GND1
Pin4
Null
/
Pin5
Null
/
Pin6
GND2
Teamwork
communications
Pin7
GROUP-RS485-D+
Pin8
GROUP-RS485-D-
CN17
Pin1
RTU-RS485-D+
Monitoring
communications
Pin2
RTU-RS485-D-
Pin3
GND1
Pin4
Null
/
Pin5
Null
/
Pin6
GND2
Teamwork
communications
Pin7
GROUP-RS485-D+
Pin8
GROUP-RS485-D-
NO TE
The cables must be shielded cables, and the shielding layer must be reliably grounded.
Connecting Teamwork Cables
NetCol8000-A013 supports teamwork networking (hand-in-hand). In networking,
a maximum of 32 smart cooling products can be teamworked. After power-on,
choose Setting > User Menu > Teamwork Setting, and set Enable Teamwork
Resistor for the controllers of the first and last smart cooling products to Yes.
NO TICE
Smart cooling products in a teamwork group must be of the same model.