Alarm
ID
Alarm Name
System
Action
Possible Causes
Solution
214
Comp Drive DC
Overvolt Alarm
The
compressor
shuts down.
The input voltage of
the compressor drive
board is higher than
the preset threshold.
1. Check whether the
input power is
within the normal
range.
2. Use an oscilloscope
to check whether
the waveform of the
power grid is within
the normal range.
3. Replace the
compressor drive
board if it is faulty.
215
Comp Drive DC
Undervolt Alarm
The
compressor
shuts down.
The input voltage of
the compressor drive
board is lower than the
preset threshold.
1. Check whether the
input power is
within the normal
range.
2. Use an oscilloscope
to check whether
the waveform of the
power grid is within
the normal range.
3. Replace the
compressor drive
board if it is faulty.