Menu
Name
Default
Value
Settings Range
Run Time out Thres
30000 h
20000 h to
40000 h
Start Low Press Mask
Time
360s
0 to 600s
Setting > Admin Menu
> Alarm Setting >
Indoor Fan
Run Time out Alarm
Enable
Enable/Disable
Run Time out Thres
50000 h
30000 h to
80000 h
Setting > Admin Menu
> Alarm Setting >
Outdoor Fan
Fan1 Run time out
Alarm
Enable
Enable/Disable
Fan1 Run time out
Thres
40000 h
30000 h to
80000 h
Setting > Admin Menu
> Alarm Setting > Main
board
Undervolt Thres
85%
83% to 100%
(220 V)
Overvolt Thres
110%
100% to 112%
(240 V)
Over Freq Thres
63 Hz
61 Hz to 63 Hz
Under Freq Thres
47 Hz
47 Hz to 49 Hz
Air Filter RT out
Alarm
Enable
Enable/Disable
Air Filter RT out
Alarm
4320 h
2160 h to 6480 h
Smoke Sensor Alarm
Enable
Enable/Disable
Floor Water Alarm
Enable
Enable/Disable
Fire Alarm
Enable
Enable/Disable
Setting > Admin Menu
> Alarm Setting >
Electric Heater
Run Time out Alarm
Enable
Enable/Disable
Run Time out Thres
30000 h
20000 h to
40000 h
Setting > Admin Menu
> Alarm Setting > Wet
Film Humidifier
Humid RT out Alarm
Enable
Enable/Disable
Humid RT out Thres
8760 h
4380 h to 17520
h
Pump RT out Alarm
Enable
Enable/Disable
Pump RT out Thres
40000 h
10000 h to
50000 h
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
E Controller Menu
Issue 02 (2020-11-09)