Step 10 After power-on again, tap
on the home screen, and tap Yes on the start
confirmation screen displayed.
Step 11 On the home screen, choose Maintain > Diagnostic Mode > Enter and set the
compressor speed to 3000rpm. After 15 minutes, choose Run > Device Run State.
Check whether the suction pressure, discharge pressure, EEV suction superheat
degree, and supercool is in reasonable range.
Table 5-6 Running parameters
Outdoor
Ambient
Temperature
Normal
Discharge
Pressure
Range
Normal
Suction
Pressure
Range
Reasonable
Suction
Superheat
Degree
Supercool
Below 15°C
1.5–2.5 MPa
0.7–1.2 MPa
4–10°C
3–5°C
15–35°C
1.5–3.1 MPa
35–45°C
2.5–3.8 MPa
Above 45°C
3.1–4.15 MPa
Step 12 Enter the diagnostic mode and set the compressor rotational speed to 0 rpm. Exit
the diagnostic mode.
Step 13 Power on the equipment, choose Maintain > Performance Maintain on the home
screen, and clear the total runtime of the EEV.
----End
5.4.2 Replacing Outdoor Unit Components
5.4.2.1 Replacing an Outdoor Fan
Prerequisites
●
An outdoor fan needs to be replaced.
●
A spare outdoor fan of the same model is available and functional.
Context
●
Tools: Phillips screwdriver, small wrench, socket wrench, cable tie, and
diagonal pliers.
●
Preparation: Power off the outdoor unit.
Procedure
Step 1 Turn off the indoor unit circuit breaker and circuit breaker in the power
distribution cabinet.