Appearance Introduction
Figure 2-7 Appearance introduction
(1) Fan
(2) Pipe stop valve and protective cover
(3) Handle
(4) Electric control box
Cooling Components
The standard outdoor unit is composed of the DC variable-frequency compressor,
oil separator, filter, DC fan and other cooling components.
●
Compressor
The DC variable-frequency compressor provides the cooling capacity ranging
from 35% to 100%.
●
Oil separator
It is an oil-gas separator which separates the lubricant brought out due to
exhaustion of the compressor and brings back the separated lubricant to the
compressor.
●
Filter
It absorbs water from the refrigerant pipes and filters the foreign matter,
which reduces component damage rates and improves operating efficiency
and reliability. It is installed in the outdoor unit and easy to maintain.
●
Fan
The DC axial fan is used, which supports stepless speed adjustment.
2.2.2.3 Controller
Appearance
The controller uses an LCD with a white backlight to display the working status,
sensor data, and running status and runtime of the key components for the smart
cooling product. The user-friendly interface is protected by multiple levels of
passwords to avoid illegal operations. The controller provides automatic recovery
after a power-off, overvoltage/undervoltage protection, and audible/visual
alarming. It can adjust the preset parameters and running parameters based on
the actual conditions to ensure that the smart cooling product operates according
to site requirements. The following shows the controller.
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
2 Product Description
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
18