Item
NetCol5000-A035
NetCol5000-A025
Airflow
6800 m
3
/h
4600 m
3
/h
Air filter
G4 filter
G4 filter
Dimensions (H x D x
W)
b
2000 mm x 600 mm x
1100 mm
2000 mm x 600 mm x
1100 mm
a: Indoor dry-bulb temperature: 37.8°C. Wet-bulb temperature: 20.8°C.
Condensing temperature: 45°C.
b: Frames can be used to expand the depth to 1200 mm, while top supports can
be used to top frame to 2200 mm.
NO TICE
● When the total load of servers, relative to a single smart cooling product, is less
than 10 kW, smart cooling products that have heating and humidification
functions or partial heating and humidification functions are recommended.
● The condensate pump is mandatory for scenarios where pipes are routed from
the top or if it is required by the customer.
Table 2-9 Optional Parameters of NetCol5000-A035
Item
NetCol5000-
A035H512D2
E120E1
NetCol5000-
A035H512D2
E120E0
NetCol5000-
A035H512D2
0020E1
NetCol5000-
A035H512D2
0020E0
Max Current
32 A
32 A
26 A
26 A
Condensate
pump
Yes
No
Yes
No
Reheat
Yes
Yes
No
No
Humidify
Yes
Yes
No
No
Reheating
capacity
6.0 kW
6.0 kW
N/A
N/A
Humidifying
capacity
3.0 kg/h
3.0 kg/h
N/A
N/A
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
2 Product Description
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
22