Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
07
Retur
n-air
3
T/H
brd
com
m
faile
d
Majo
r
N/A
The
alarm
is
genera
ted.
1. The cables to the
T/H sensor are
loose or
damaged.
2. The DIP switch
of the T/H
sensor is set
incorrectly.
3. The T/H sensor
is faulty.
4. The
communication
port of the
control board is
faulty.
1. Check the
cables to the
T/H sensor.
2. Set the DIP
switch of the
T/H sensor
correctly.
3. Maintain or
replace the T/H
sensor.
4. Maintain or
replace the
control board.
a0
08
Com
p HP
Majo
r
4.25
MPa
The
alarm
is
genera
ted,
and
the
compr
essor
shuts
down
forcibl
y.
1. The power
supply to the
outdoor unit is
lost, or a phase
is open or error.
2. The on/off signal
cables of the
outdoor unit are
disconnected.
3. The condenser
fins are blocked.
4. The outdoor fan
or fan driver is
damaged.
5. The cables to the
high pressure
switch are loose
or damaged.
6. The high
pressure switch
is faulty.
7. The solenoid
valve is faulty.
8. The refrigerant is
overfilled.
1. Check the
power supply of
the outdoor
unit.
2. Check the
on/off signal
cables of the
outdoor unit.
3. Clean the
condenser fins.
4. Maintain or
replace the
outdoor unit or
unit driver.
5. Check the
cables to the
high pressure
switch.
6. Maintain or
replace the high
pressure switch.
7. Maintain or
replace the
solenoid coil or
the solenoid
valve.
8. Decrease
certain amount
of refrigerant.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
162