Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
09
Com
p HP
lock
Critic
al
4.25
MPa
The
alarm
is
genera
ted,
and
the
compr
essor
is
locked
and
not
allowe
d to be
started
.
The a008 comp HP
alarm is generated
frequently.
Reference to the
solutions for the
a008 comp HP
alarm.
a0
10
Com
p LP
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
compr
essor
shuts
down
forcibl
y.
1. The refrigerant
leaks.
2. The solenoid
valve is faulty.
3. The cables to the
low press switch
are loose or
damaged.
4. The low press
switch is
faulty.The dryer
filter is blocked.
5. The expansion
valve is blocked.
6. The indoor fans
are faulty.
1. Check for any
leakages. Fill
refrigerant after
maintenance or
replacement.
2. Maintain or
replace the
solenoid coil or
the solenoid
valve.
3. Check the
cables to the
low press
switch.
4. Maintain or
replace the low
press switch.
5. Maintain or
replace the
dryer filter.
6. Maintain or
replace the
expansion valve.
7. Maintain or
replace the
indoor fans.