Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
33
Powe
r
phas
e C
unde
rvolt
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply voltage is
lower than the
power undervolt
alarm thres.
2. If a voltage
jumper is used,
possibly it is
incorrectly
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.
a0
34
Powe
r
overf
req
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply frequency
is too high.
2. The SPD three-
phase test board
is faulty.
1. Check the
power supply
frequency.
2. Replace the SPD
three-phase test
board.
a0
35
Powe
r
unde
rfreq
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply frequency
is too low.
2. The SPD three-
phase test board
is faulty.
1. Check the
power supply
frequency.
2. Replace the SPD
three-phase test
board.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
169