Paramete
r
Description
Configuration Principle Default
Value
Teamwork
mode
Set the teamwork mode.
The options include Smart
and iCooling.
Determine whether to
enable the iCooling
mode based on onsite
heat load variations. If
the heat load varies
greatly, it is
recommended that you
enable the iCooling
mode. The parameter
can only be modified on
the ECC WebUI and
cannot be modified on
the smart cooling
product screen.
Smart
Enable
L1/L2
linkage
Enable or disable L1/L2
linkage.
Set this parameter based
on site requirements.
The parameter can only
be modified on the ECC
WebUI and cannot be
modified on the smart
cooling product screen.
Disable
Network
Networking mode for the
teamwork.
Networked over CAN.
Over CAN
Total
number of
units
Number of the smart
cooling products in this
group (1 to 32 can be set).
Total number of the
smart cooling products
in this group.
3
Number
of running
units
Number of running units in
a group. The value ranges
from 1 to Total number of
units.
The master unit assigns
the devices to be active
units by the device
number, beginning with
the address 1 until to
Number of running
units. The rest will
become the standby
ones.
2
Rotation
Disable or enable the
active and standby smart
cooling products to change
identity after a certain
time, maximizing their
service life.
This function is
recommended when the
heat is even.
Disable
Rotation
period
Rotation days (1-30).
7 by default.
7 days
Rotation
time
24 hours in a day (0-23)
0 by default.
0
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
99