Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
58
Com
p
disch
arge
HP
lock
Critic
al
4.25
MPa
The
alarm
is
genera
ted,
and
the
compr
essor
is
locked.
Can
not
start
the
locked
compr
essor.
The a057 comp
discharge HP alarm
is generated
frequently.
Reference to the
solutions for the
a057 comp
discharge HP
alarm.
a0
59
Sucti
on
pres
sens
or
fault
Majo
r
N/A
The
alarm
is
genera
ted.
1. The cables to the
press sensor are
loose or
damaged.
2. The press sensor
is faulty.
1. Check the
cables to the
press sensor.
2. Replace the
press sensor.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
177