Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
51
Hot-
aisle
HT
Critic
al
45°C
The
alarm
is
genera
ted,
and
the
rotatio
nal
speed
of the
compr
essor
increas
es.
1. The hot-aisle
T/H sensors are
located in
inappropriate
position.
2. The ambient
temp is high.
3. The hot-aisle HT
alarm thres is
inappropriate.
4. The temp
displayed is
different from
the actual temp.
5. The load is high
or the
refrigeration
capacity is
insufficient.
1. Adjust the
position of the
hot-aisle T/H
sensors.
2. Check the
ambient temp.
3. Adjust the hot-
aisle HT alarm
thres.
4. Calibrate or
replace the
abnormal T/H
sensors.
5. Add more smart
cooling product
units.
a0
52
Supp
ly-air
1
temp
invali
d
Supp
ly-air
2
temp
invali
d
Supp
ly-air
3
temp
invali
d
Majo
r
N/A
The
alarm
is
genera
ted.
1. The cables to the
temp sensor are
loose or
damaged.
2. The temp sensor
is faulty.
1. Check the
cables to the
temp sensor.
2. Maintain or
replace the
temp sensor.
a0
55
Disch
arge
temp
sens
or
fault
Majo
r
N/A
The
alarm
is
genera
ted.
1. The cables to the
temp sensor are
loose or
damaged.
2. The temp sensor
is faulty.
1. Check the
cables to the
temp sensor.
2. Maintain or
replace the
temp sensor.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
175