Paramete
r
Description
Configuration Principle Default
Value
Forced
rotation
Forced rotation specifies
whether to enable a
forcible rotation on the
group before the specified
rotation time. After a
forced rotation, the
accumulated time is
recalculated.
This item is set to No by
default. If forced
rotation is required, the
function is set to Yes.
No
Requirem
ent
control
Enable or disable the
requirement control for the
master device.
● When the requirement
control is Enable, the
master device
synchronizes data (the
temperature and
humidity control type
and set points of the
master device) to the
slave device, and all the
smart cooling products
in the group refer to the
mode delivered by the
master device.
● When the requirement
control is Disable, the
master device does not
synchronize data to the
slave device, and all the
smart cooling products
operate based on their
own requirements, not
referring to the mode
delivered by the master
device.
The requirement control
function is
recommended for the
following scenario: In
one teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
Disable
Cascade
After the requirement
control is enabled, you can
configure Cascade. The
cascade function starts
standby smart cooling
products if the active one
cannot meet the
refrigerating requirements.
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Large ring
cooling
capacity P
Proportion coefficient in
L1/L2 linkage PID control.
You are not
recommended to change
the value.
0.10
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
100