4.6.1 Querying Parameters
4.6.1.1 Querying Temperature and Humidity Curves
Context
The T/H Curve screen displays temperature and humidity curves showing the
recent temperature and humidity changes. You can choose to display the curves
showing data changes of recent one hour, one day, seven days, or 30 days.
Procedure
Step 1 On the home screen, tap T/H Curve.
is displayed.
Figure 4-18 T/H curve screen
NO TE
● The temperature curve (upper) and the humidity curve (lower) are displayed on the
same screen. The abscissa shows time. The temperature set point is the midpoint
temperature on the upper ordinate while the humidity set point is the midpoint
humidity on the lower ordinate.
● The temperature and humidity curves show the current average temperature and
humidity of the control type.
● You can tap
and
to zoom in or out the range of the temperature and humidity
ordinate. The midpoint temperature is the temperature set point and the midpoint
humidity is the humidity set point after the ordinate range is zoomed in or out.
● You can view the temperatures from (temp set point - 3°C) to (temp set point + 3°C) at
least and from (temp set point - 30°C) to (temp set point + 30°C) at most.
● You can view the humidity from (humidity set point - 5%) to (humidity set point + 5%)
at least, and from (humidity set point - 50%) to (humidity set point + 50%) at most.
Specific humidity fluctuation range displayed varies according to different models of
smart cooling products.
----End