Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
78
Full
wate
r
Critic
al
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The cables to the
high float are
loose or
damaged.
2. The high float is
faulty or stuck.
3. The cond pump
is faulty, or the
drainage
capacity
decreases if
configured.
4. The drainpipe of
the cond pump
is blocked if the
cond pump is
configured.
5. The internal
drainpipe or the
pipeline is
blocked if no
cond pump is
configured.
1. Check the
cables to the
high float.
2. Maintain or
replace the high
float or clear
the obstacles.
3. Maintain or
replace the
cond pump.
4. Clear the
obstacles in the
drainpipe of the
cond pump.
5. Clear the
internal
drainpipe.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
184