Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
49
Supp
ly-air
LT
Warn
ing
5°C
The
alarm
is
genera
ted.
1. The load is low.
2. The ambient
temp is low.
3. The supply-air LT
alarm thres is
inappropriate.
4. The temp
displayed is
different from
the actual temp.
5. The air filters are
blocked.
1. Please consult
Huawei
technical
support.
2. Check the
ambient temp.
3. Adjust the
supply-air LT
alarm thres.
4. Calibrate or
replace the
abnormal
sensors.
5. Maintain or
replace the air
filters.
a0
50
Cold-
aisle
HT
Critic
al
40°C
The
alarm
is
genera
ted,
and
the
rotatio
nal
speed
of the
compr
essor
increas
es.
1. The cold-aisle
T/H sensors are
located in
inappropriate
position.
2. The ambient
temp is high.
3. The cold-aisle
HT alarm thres is
inappropriate.
4. The temp
displayed is
different from
the actual temp.
5. The load is high
or the
refrigeration
capacity is
insufficient.
1. Adjust the
position of the
cold-aisle T/H
sensors.
2. Check the
ambient temp.
3. Adjust the cold-
aisle HT alarm
thres.
4. Calibrate or
replace the
abnormal T/H
sensors.
5. Add more smart
cooling product
units.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
174