Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
36
Powe
r
phas
e
loss
Critic
al
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power grid
is unstable.
2. The surge
protection board
is faulty if
configured.
3. The main power
supply or the
comp driver
supply is
connected
improperly.
1. Check the
power grid.
2. Maintain or
replace the
surge protection
board.
3. Check the main
power supply or
cables to the
comp driver.
a0
37
Powe
r
phas
e
rever
se
CRITI
CAL
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power grid
is unstable.
2. The surge
protection board
is faulty.
1. Check the
power grid.
2. Maintain or
replace the
surge protection
board.
a0
38
Liqui
d
pipe
temp
sens
or
fault
MAJ
OR
-
The
alarm
is
genera
ted.
1. Cables to the
liquid pipe temp
sensor are not
properly
connected.
2. The liquid pipe
temp sensor is
faulty.
1. Maintain or
replace the
liquid pipe temp
sensor.
2. Check cables to
the liquid pipe
temp sensor.
a0
39
Ctrl
point
sens
or
disab
led
Majo
r
N/A
The
alarm
is
genera
ted,
and
the
system
shuts
down.
All the T/H sensors
of the control point
are disabled.
Enable the T/H
sensors of the
control point or
change the control
point.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
6 System Operation and Maintenance
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
170