●
T/H Curve
Indicates curves for recent (time optional) temperature and humidity changes.
●
Teamwork
Sets and checks teamwork control information based on the requirements of
the smart cooling product.
●
Running
Checks the component status, system parameters, and the name, control and
operating status, and other related information of the components in the
current smart cooling product system.
●
Alarms
Checks the active and historical alarms of the smart cooling product, and
deletes the historical alarms.
●
Settings
Sets the involved parameters for the operation of the smart cooling product.
●
Maint
Checks or deletes the logs or component total runtime/run factor, manually
diagnoses each component, calibrates the sensor and touch screen, exports
data, and upgrades the system.
●
About
Checks the model, manufacturer, monitoring version, detail version
information, and electronic label of the ACC.
4.5 Power-On Commissioning
4.5.1 Quick Settings
Prerequisites
After the system is powered on, the LCD is started, and the progress bar in the
startup screen is full:
●
For initial power-on, the system enters the quick setting screen. Set the
parameters by following the instructions in this section.
●
For non-initial power-on, the LCD automatically enters the home screen as
shown in
Procedure
Step 1 Set the language and tap Next, as shown by (1) in
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
89