Figure 4-8 Setting temperature and humidity values
Step 2 Set the parameters by referring to
NO TE
You are not recommended to modify the parameters not listed in
Table 4-3 Parameter description
Parameter
Description
Configuration Principle
T/H control
type
Sets Cold-aisle,
Hot-aisle, Return-
air, or Supply-air
as required. The
temperature and
humidity set points
correspond to the
selected control
type can be set.
● Return-air: For a hot aisle, select
Return-air to control the
temperature and humidity around
the air return vent of the smart
cooling product.
● Supply-air: For a cold aisle, select
Supply-air to control the
temperature and humidity around
the air supply vent of the smart
cooling product.
● Cold-aisle: For a cold aisle, select
Cold-aisle to control the temperature
and humidity of the aisle. The
temperature and humidity values
come from the humidity and
temperature sensor in the aisle.
● Hot-aisle: For a hot aisle, choose
Hot-aisle to control the temperature
and humidity of the aisle. The
temperature and humidity values
come from the humidity and
temperature sensor in the aisle.
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width)
4 ACC Introduction
Issue 17 (2020-10-22)
Copyright © Huawei Technologies Co., Ltd.
93