Al
ar
m
ID
Alar
m
Alar
m
Seve
rity
Defau
lt
Value
Impac
t
Possible Cause
Solution
a0
30
Powe
r
phas
e C
overv
olt
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply voltage is
higher than the
power overvolt
alarm thres.
2. If a voltage
jumper is used,
possibly it is
incorrectly
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.
a0
31
Powe
r
phas
e A
unde
rvolt
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply voltage is
lower than the
power undervolt
alarm thres.
2. If a voltage
jumper is used,
possibly it is
incorrectly
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.
a0
32
Powe
r
phas
e B
unde
rvolt
MAJ
OR
-
The
alarm
is
genera
ted,
and
the
system
shuts
down.
1. The power
supply voltage is
lower than the
power undervolt
alarm thres.
2. If a voltage
jumper is used,
possibly it is
incorrectly
connected.
3. If a toggle
switch is used,
possibly it is
incorrectly set.
1. Check the
power supply
voltage.
2. Maintain or
replace the
voltage jumper.
3. Correctly set the
toggle switch.