10. Verify the serial number and model string data information copied onto the new board by
doing the following:
a.
Boot to EFI.
b.
Enter
Service
mode:
Shell> sysmode service
Current System Mode: ADMIN
You are now in SERVICE mode.
c.
Use the
sysset
command to verify that all values are set:
Shell> sysset
System Information:
Manufacturer: hp
Product Name: server rx2660
Product Number: AB463A
Secondary Product Number is Identical
Serial number: SGH43442VB
Secondary Serial Number is Identical
UUID: 3C33C58E-2E5A-11D8-A33B-4188C0AEFAE2 (Valid)
Secondary UUID is Identical
Product ID: 0x601
NOTE:
Due to the type of server you purchased, your
sysset
output may not exactly
match the output shown here.
11. Verify the System Insight Display replacement and operation by using the following system
utilities:
•
Use the iLO 2 MP
DF
command to check the customer replaceable unit (CRU) ID of the
System Insight Display.
Removing and Replacing the Fan Carrier Assembly
The server contains an fan carrier assembly, located behind the front bezel, that houses eight of
the 12 server fans if you have a Data Center rx2660 server; or four of the six fans if you have an
Office Friendly Server.
WARNING!
Ensure that the system is powered off and all power sources are disconnected
from the server prior to performing this procedure.
Voltages are present at various locations in the server whenever an ac power source is connected.
This voltage is present even when the main power switch is off.
Failure to observe this warning can result in personal injury or equipment damage.
CAUTION:
Observe all ESD safety precautions before attempting this procedure. Failure to
follow ESD safety precautions can result in damage to the server.
Removing the Fan Carrier Assembly
This procedure applies to the Data Center rx2660 server fan assembly, or the Office Friendly
server fan assembly.
To remove the fan carrier assembly, follow these steps:
1.
Power off the server, and disconnect the power cables. See
“Powering On and Powering Off
the Server” (page 78)
.
2.
If rack mounted, slide the server completely out from the rack. See
“Extending the Server
from the Rack” (page 143)
.
3.
Remove the top cover. See
“Removing the Top Cover” (page 144)
.
162
Removing and Replacing Server Components