The supported configuration of the Office Friendly server is two power supplies. You can install
or replace a hot-swappable power supply using the procedures in this section when power is on
or off.
CAUTION:
Observe all ESD safety precautions before attempting this procedure. Failure to
follow ESD safety precautions can cause damage to the server.
NOTE:
A hot-swappable device does not require that you interact with the operating system
before the device is removed from, or installed into, the server.
Power to the server does not have to be off to install or replace a hot-swappable power supply
as long as there is another power supply installed in the server, and is connected to a power
source.
Power Supply Loading Guidelines
The supported configuration for the Data Center server requires that at least one power supply
be installed in slot P1 or slot P2. You can install a second, optional, hot-swappable power supply
to provide 1+1 capability. The right side (viewed from the rear of the server) hot-swappable
power supply is identified as P1, and the second hot-swappable power supply to the left is P2.
See
Figure 6-11
.
The supported configuration for the Office Friendly server requires that both power supplies be
installed.
CAUTION:
When a second power supply is not used (Data Center server only), the empty
power supply slot must remain covered with the supplied metal filler panel. Failure to observe
this caution can result in damage due to overheating.
Install the hot-swappable power supply in the server before attaching the new power cord.
Failure to observe this precaution can result in damage to the server.
NOTE:
The Office Friendly server can run on only one power supply. However, two power
supplies must be installed to meet the acoustic requirements for an Office Friendly server. Replace
a failed power supply as soon as possible.
Removing a Power Supply
To remove a power supply, follow these steps:
1.
Move the cable management arm from the rackslide nearest the power supplies enough to
allow access to the power supplies.
2.
Remove the power cord plug from the power supply receptacle.
3.
Grasp the power supply handle and push the locking tab down with your thumb to release
the power supply from the socket on the power supply riser board (1).
4.
Supporting the power supply with both hands, pull the power supply out of the server (2).
154
Removing and Replacing Server Components