SPECIFICATIONS
Input
Nominal voltage
120 VAC (-15%, +10%), 230 VAC (-15%, +10%), 24 VDC (-10%, +20%)
Nominal power consumption
24 VDC: 2 W; 230 VAC: 4 VA
Nominal frequency
50 to 60 Hz
Start time
Manual START function: 50 ms (-25%, +50%); Automatic START function: 1 s (-25%,
Nominal voltage at S11
24 VDC with 35 mA current ±25% (provided by control module)
Minimum voltage at S11
21 VDC when activated
Cable resistance between S11/S12
and S21/S22
68 • (max.)
Output
Contact complement
3 NO, 1 NC contacts
Response time
After opening of input (S11/12 or S21/22): 25 ms; Opening in supply circuit (L1(+)/A1): 50
Contact type
Safety relay, positive-guided
Switching capability
Power factor = 1 with resistive load
Current range (min. to max.)
1 mA to 10 A (see caution)
Voltage range (min. to max.)
0.1 to 250 VAC/DC
Typical Electrical Life Espectancy
3A
5A
10A
Power factor = 1 at 230 VAC/DC (note 1)
1,000,000 operations
500,000 operations
220,000 opeerations
Typical Electrical Life Expectancy
0.3
0.5
0.7
1.0
Limitation factor (note 2)
0.45
0.70
0.85
1.00
Operating frequency
600 switching cycles/h
Fuse rating
6 A gL (max.)
Mechanical life
Ten million switching operations
General
Temperature range
-15°C to +55°C (5°F to 131°F) at 90% humidity (max.)
Sealing
Housing IP 40; Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
Amplitude 0.35 mm: Frequency 10 to 55 Hz
Conductor connection
1 x 4 mm² solid (max.) [12 AWG] ot 2 x 1.5 mm² (max.) [16 AWG] stranded wire with sleeve
Conductor attachment
Removable block temrinals with M3,5 screws; wire contacts are enclosed to prevent
Mounting
Quick install rail mounting EN 50022-35
Weight
450 g (0.99 lb.)
NOTE 1: Install arc
suppression device across
load to avoid module contact
arcing and ensure specified
relay life expectancy.
NOTE 2: Total operations =
operations at power factor 1
multiplied by the limitation
factor. if the power factor is
0.5 at 230 vac, 3A
(1,000,000 operations), the
limitation factor is 0.70.
1,000,000 x 0.70 = 700,000
total operations.
FIG 1. CONTACT LIFE FOR
100% RESISTIVE LOAD
(typical)
(note 1)
power factor = 1 (cos
ϕ
)
FIG 2. LIMITATION FACTOR
FOR INDUCTIVE LOADS
(note 2)
power factor < 1 (cos
ϕ
)
CONTACT DAMAGE
To ensure the 1 mA capability during the lifetime of the contact, NEVER exceed 300 mA and 60 V.
Failure to comply with these instructions will result in product damage.
Содержание SYA14 Series
Страница 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Страница 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 84: ......
Страница 158: ......
Страница 160: ......
Страница 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Страница 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Страница 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Страница 263: ...PK 107007 1 EN FR26 GLO 298 Printed in France Safety Mat Installation Manual FF SM Series Safety Mat PK 107007 Issue 1 ...
Страница 264: ...ii Honeywell PK 107007 01 EN FR26 GLO 0298 Printed in France For application help see Warranty Information ...
Страница 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Страница 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Страница 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Страница 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...