107018-04 EN FR26 GLO 1198 Printed in Germany
7
APPLICATION EXAMPLES
FIG 10. DUAL CHANNEL EMERGENCY STOP CIRCUITRY (WITH CROSS-FAULT MONITORING)
Start
L1
Honeywell
FF-SRS 5988
Emergency
stop
N
Y1 Y2
X1 X2
S33
S11
A3
(+)
S34
(A)
(B)
A4
(-)
(C)
Machine
Control
Power
Fuse
Fuses
This circuit has redundancy in the emergency-stop control circuit and therefore offers the highest
possible safety level.
FUNCTIONAL DESCRIPTION:
After activation of the Emergency-stop push button, the K1 and K2 LED’s will turn OFF, indicating that the
two internal safety relays K1 and K2 are de-energized. The normally open safety outputs 13/14... 63/64 will
open.
There exist two different start modes:
Manual start mode
1. After removing the stop condition, press and release the START push button to restart the safety control
module.
2. The K2 and K3 LED’s will turn ON indicating that the safety relays K2 and K3 are energized. The six
normally open safety contacts will close and the normally closed monitoring contact will open allowing the
machine to operate.
Automatic start mode
1. After removing the stop condition, the safety control module will reset within 1 sec.
The K2 and K3 LED’s will turn ON indicating that the safety relays K2 and K3 are energized. The six
normally open safety contacts will close and the normally closed monitoring contact will open allowing the
machine to operate.
APPLICATION NOTES:
NOTE (A):
Dual channel safety devices:
This may be an emergency stop push button in series with dual output safety switching devices (OSSD)
such as
- safety light curtains (FF-SB, FF-LS),
- safety mat (FF-SM),
- single beam (FF-SPS), modular safety light curtains (FF-SC),
- safety laser scanner (FF-SE),
- dual output safety limit or interlock switches (for example, 2CLS and GK, see fig. 12).
NOTE (B):
Y1 and Y2 are jumpered if no external contactors have to be monitored
NOTE (C):
Start mode:
Manual start mode: Insert start push-button between S33/S34; no jumper must be set between X1/X2
Automatic start mode: Insert jumper between X1/X2
IMPROPER AUTOMATIC START MODE IN PERIMETER GUARDING APPLICATIONS
•
If the module is in the automatic start mode, another part of the safety control circuitry must keep the
latched function engaged.
Failure to comply with these instructions could result in death or serious injury.
Содержание SYA14 Series
Страница 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Страница 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 84: ......
Страница 158: ......
Страница 160: ......
Страница 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Страница 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Страница 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Страница 263: ...PK 107007 1 EN FR26 GLO 298 Printed in France Safety Mat Installation Manual FF SM Series Safety Mat PK 107007 Issue 1 ...
Страница 264: ...ii Honeywell PK 107007 01 EN FR26 GLO 0298 Printed in France For application help see Warranty Information ...
Страница 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Страница 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Страница 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Страница 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...