FF-SRD5985 Series
ISSUE 1
PK 107013-01
2
PK 107013-01-EN FR26 GLO 398 Printed in Germany
SPECIFICATIONS
Input
Nominal voltage
120 VAC (-15%, +10%), 230 VAC (-20%, +10%), 24 VDC (-10%, +20%)
Nominal consumption
120 VAC, 230 VAC: 4 VA; 24 VDC: 2.5 W
Nominal frequency
50 to 60 Hz
Control contacts
Two NO contacts
Nominal voltage at S13/S23
24 VDC / 0VDC (provided by control module)
Nominal input current between S13/S14 and S23/S24
35 mA (ensure 10 mA switching capability with sensors connected to two inputs)
Time required for simultaneous contact closure
of S13/S14 and S23/S24
3 sec (max.)
Output
Contact complement
2 NO contacts
Contact type
Safety relay, positive-guided
Response time
Activation/deactivation by inputs S13/S14 and S23/S24 : 30 ms
Switching Capability
Power factor = 1 with resistive load
Current Range (min. to max.)
1 mA to 10A (see caution)
Voltage Range (min. to max.)
0.1 to 250 VAC/DC
Typical Electrical Life Expectancy
3A
5A
10A
Power factor = 1 at 230 VAC/DC (note 1)
1,000,000 operations
500,000 operations
220,000 operations
Typical Power Factor (cos
ϕϕ
)
0.3
0.5
0.7
1.0
Limitation Factor (note 2)
0.45
0.70
0.85
1.00
Fuse rating
6 A gL (max.)
Mechanical life
Ten million switching operations
General
Temperature range
-15
°
C to + 55
°
C (5
°
F to 131
°
F) at 90% humidity (max.)
Sealing
Housing IP 40 Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
Amplitude 0.35 mm; Frequency 10 to 55 Hz
Conductor connection
1 x 4 mm
2
solid (max.) [12 AWG] or 2 x 1.5 mm
2
(max.) [16 AWG] stranded wire with sleeve DIN
46288
Conductor attachment
M 3,5 screws terminals; wire contacts are enclosed to prevent electrical shock
Mounting
Quick install rail mounting EN 50022-35
Weight
450 g (0.99 lb.)
NOTE 1: Install arc suppression
device across load to avoid
module contact arcing and
ensure specified relay life
expectancy.
NOTE 2:
Total operations =
operations at power factor 1
multiplied by the limitation
factor. If the power factor is 0.5
at 230 vac, 3A (1,000,000
operations), the limitation factor
is 0.70. 1,000,000 x 0.70 =
700,000 total operations.
FIG 1. CONTACT LIFE FOR 100%
RESISTIVE LOAD (typical) (note 1)
power factor = 1 (cos
ϕ
)
FIG 2. LIMITATION FACTOR FOR INDUCTIVE
LOADS (note 2)
power factor < 1 (cos
ϕ
)
CONTACT DAMAGE
To ensure the 1 mA capability during the lifetime of the contact, NEVER exceed 300 mA and 60 V.
Failure to comply with these instructions will result in product damage.
Содержание SYA14 Series
Страница 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Страница 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 84: ......
Страница 158: ......
Страница 160: ......
Страница 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Страница 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Страница 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Страница 263: ...PK 107007 1 EN FR26 GLO 298 Printed in France Safety Mat Installation Manual FF SM Series Safety Mat PK 107007 Issue 1 ...
Страница 264: ...ii Honeywell PK 107007 01 EN FR26 GLO 0298 Printed in France For application help see Warranty Information ...
Страница 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Страница 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Страница 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Страница 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...