107022-14 EN FR26 GLO 0100 Printed in Germany
36
Figure 5-2 Control Unit Printed Circuit Board
Use the tables below to determine the operating status of the protective safety equipment. To use the acoustic signal to
determine the protective safety equipment status, the buzzer switch must be set to the ON position (see figure above).
Table 5-2 FF-LS Status in Automatic Restart Mode (with power ON)
Beam Condition
LED And Buzzer Status
FF-LS Status and Remedy
CLEAR
•
Red LEDs 5 and 7 flicker.
•
Yellow LEDs 4 and 6 are always illuminated.
•
Acoustic signal NOT present. (1)
•
The FF-LS is operating correctly.
•
Safety output contacts X1 and X2 are closed.
INTERRUPTED
•
Red LEDs 5 and 7 flicker.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal present (short interval). (1)
•
The FF-LS is operating correctly, but needs a
clear beam status.
•
Safety output contacts X1 and X2 are open.
(1) Buzzer switch ON.
Table 5-3 FF-LS Status in Start and Restart Interlock (Manual) Mode
Beam Condition
LED And Buzzer Status
FF-LS Status and Remedy
AT POWER UP
CLEAR
•
Red LEDs 5 and 7 are always illuminated.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal is always present. (1)
•
The FF-LS is operating correctly but needs to
be restarted.
•
Safety output contacts X1 and X2 are open.
INTERRUPTED
•
Red LEDs 5 and 7 are always illuminated.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal is always present. (1)
•
An object within the sensing field forbids the
effective restart of the FF-LS.
•
Safety output contacts X1 and X2 are open.
DURING NORMAL OPERATION
CLEAR
•
Red LEDs 5 and 7 are illuminated.
•
Yellow LEDs 4 and 6 are always illuminated.
•
Acoustic signal NOT present. (1)
•
The FF-LS is operating correctly.
•
Safety output contacts X1 and X2 are closed.
INTERRUPTED
THEN RELEASED
•
Red LEDs 5 and 7 are always illuminated.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal always present. (1)
•
The FF-LS is operating correctly but needs to
be restarted.
•
Safety output contacts X1 and X2 are open.
(1) Buzzer switch ON.
5.3
Troubleshooting
POWER APPLIED TO MACHINE CONTROL SYSTEM
Before intervention, turn off and disconnect power from FF-LS Series safety light curtain and machine.
Failure to comply with these instructions could result in death or serious injury.
Terminals
Output contact fuses
LED indicators
(supply voltage)
LED Indicators
(system condition)
Function
Содержание SYA14 Series
Страница 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Страница 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 84: ......
Страница 158: ......
Страница 160: ......
Страница 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Страница 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Страница 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Страница 263: ...PK 107007 1 EN FR26 GLO 298 Printed in France Safety Mat Installation Manual FF SM Series Safety Mat PK 107007 Issue 1 ...
Страница 264: ...ii Honeywell PK 107007 01 EN FR26 GLO 0298 Printed in France For application help see Warranty Information ...
Страница 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Страница 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Страница 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Страница 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...