FF-SR05936 Series
ISSUE 1
PK 107010-01
PK 1070-01-EN FR26 GLO 398 Printed in Germany
3
FIG 3. CURRENT VS. TEMPERATURE LIMIT
-22
32 50 68 86 104 122 140 T(°F)
Ambient Temperature
FSR051
Figure 3. displays the maximal recommended external
temperature versus the total load of all the safety module
contacts. To use this curve, do the following:
(1)
Follow the horizontal line from the value (vertical axis)
equal to the current inside the safety module contacts
and note intersection of the appropriate curve.
(2)
Follow the intersection point down to determine the
maximal recommended ambient temperature. (Ex: 4 A
current inside each two safety contacts, then T = 43
°
C
(109
°
F).
If the module is located in a higher temperature
environment, the lifetime of the electronic components may
be reduced. Ventilation of the cabinet may be required.
MECHANICAL INSTALLATION
The FF-SR05936 must be installed inside a NEMA 3 (IEC
IP54) rating enclosure or better. The module can be
clipped easily onto a 45mm width DIN rail (see figures 4 and
5 below for installation and removal).
FIG 4. MOUNTING DIMENSIONS
(for reference only)
FIG 5. INSTALLATION DIAGRAM
CONTROL RELIABILITY
“Control Reliability” means that “the device, system or
interface shall be designed, constructed and installed such
that a single component failure within the device, interface
or system shall not prevent normal stopping action from
taking place but shall prevent a successive machine cycle.”
(ANSI B11.19-1990, 5.5)
OSHA 29 CFR 1910.217 states that “the control system
shall be constructed so that a failure within the system does
not prevent the normal stopping action from being applied
to the press when required, but does prevent initiation of a
successive stroke until the failure is corrected. The failure
shall be detectable by a simple test, or indicated by the
control system.”
Honeywell uses self-checking techniques which combine
reliability with safety. This means that a faulty component in
our system will make the safety control modules fail in a
safe mode.
FIG 6. MODULE FRONT PANEL
A2
(-)
A1
(+)
11
21
33
12
43
Z1
Z2
Honeywell
FF-SR05936
22
34
44
A1/A2
Zero
Motion
Continuity
Z1/Z2
FSR054
a Width: 45 mm 1.77 in.
b Height: 74 mm 2.91 in.
c Depth: 121 mm 4.76 in
Содержание SYA14 Series
Страница 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Страница 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 84: ......
Страница 158: ......
Страница 160: ......
Страница 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Страница 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Страница 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Страница 263: ...PK 107007 1 EN FR26 GLO 298 Printed in France Safety Mat Installation Manual FF SM Series Safety Mat PK 107007 Issue 1 ...
Страница 264: ...ii Honeywell PK 107007 01 EN FR26 GLO 0298 Printed in France For application help see Warranty Information ...
Страница 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Страница 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Страница 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Страница 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...