107004-15 EN FR26 ROW 0899 Printed in France
79
IMPROPER CONNECTION OF LOAD
For safety reasons, the loads must be connected connected between terminals 2-8 and
between terminals 2-25 .
Failure to comply with these instructions could result in death or serious injury.
4.9.2 Press applications
FACTORY SETTINGS
•
The muting module is set in the conveyor mode on delivery.
•
Refer to chapter 2.4.1 Selection of the appropriate mode, to select the press mode.
•
The maximum timing tmax allowed between SM sensors is set to 1 second on delivery.
For machines different than presses, it can be modified to the following values : 2 s, 4 s, or 8 s.
•
The setting of the timing tmax also sets the muting maximum duration
∆
max. In the press mode, the
muting duration is set to 1 mn on delivery. In the press mode, it can be modified to the following values
for machines different than presses: 2, 4 or 60 mn.
•
On delivery, the muting module provides a normally closed test contact between
terminals 28 and 29. All the Honeywell protective equipment need a normally closed contact
on their test input with the exception of the FF-SCAN, the FF-LS and the FF-SPS4 which
need a normally open contact. The test output can be changed to a normally open contact.
•
Refer to chapter 2.4.2 SM inputs to select tmax and
∆
max, and refer to chapter 4.5.2 Test output to
select the appropriate test contact.
IMPROPER USE OF THE MUTING MODULE
NEVER mute the protective equipment during a dangerous phase of the machine
working cycle.
Failure to comply with these instructions could result in death or serious
injury.
SENSORS COINCIDENCE TIMING (tmax) AND MUTING DURATION (
∆
max)
On a press, both SM sensors must be activated within the following time frame : 8 ms < t
< 1s. The maximum duration
∆
max of the muting sequence must be set to 1 mn. These
are the factory settings.
Failure to comply with these instructions could result in death or serious injury.
Содержание SYA14 Series
Страница 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Страница 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Страница 84: ......
Страница 158: ......
Страница 160: ......
Страница 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Страница 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Страница 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Страница 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Страница 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Страница 263: ...PK 107007 1 EN FR26 GLO 298 Printed in France Safety Mat Installation Manual FF SM Series Safety Mat PK 107007 Issue 1 ...
Страница 264: ...ii Honeywell PK 107007 01 EN FR26 GLO 0298 Printed in France For application help see Warranty Information ...
Страница 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Страница 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Страница 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Страница 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Страница 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...