Appendix 4 - EN54-2 Options with Requirement
s
A4 - 1
997-457-000-8, Issue 8
January 2010
ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Appendix 4
EN54-2- Options with Requirements
In addition to satisfying the requirements of EN54-2
Options with Requirements, the table below defines
whether the CIE is configurable in accordance with the
mandatory or optional requirements of VdS 2540.
EN54-2 Description
VdS 2540
C.I.E.
Option
Option
Configurable?
INDICATIONS
7.10.4
Fault signal from fire protection equipment
Required
Yes
7.13
Alarm counter
Required
Yes
8.3
Fault signals from points
Optional
Yes
8.4
Total loss of power supply
Optional
No
CONTROLS
7.11.1
Delays to outputs
Optional
Yes
7.11.2
Manual or automatic switching of delays to outputs
Optional
Yes
7.12.1
Dependency on more than one alarm signal: Type A
Optional
No
7.12.2
Dependency on more than one alarm signal: Type B Required
Yes
7.12.3
Dependency on more than one alarm signal: Type C Prohibited
No
9.5
Disablement of each address point
Optional
Yes
10
Test condition
Required
Yes
OUTPUTS
7.8
Fire alarm device(s)
Required
Yes
7.9.1
Fire alarm routing equipment
Required
Yes
7.9.2
Fire alarm routing equipment with alarm confirmation Required
Yes
7.10.1
Automatic fire protection equipment: Type A
Optional
Yes
7.10.2
Automatic fire protection equipment: Type B
Optional
No
7.10.3
Automatic fire protection equipment: Type C
Required
Yes
8.9
Fault warning routing equipment
Required
Yes
11
Standardized I/O interface
Required
Yes
1
1
Interface meets VdS 2540 which requires DIN 14675 & 4662, but not full EN54-2, 11.
A1 Fault Signal From CIE
This is a VdS 2540 requirement. The CIE provides for
this EN54-2 option.
The CIE comprises a volt-free contact relay configured
as a dedicated fault output. Refer to
Section 4.4.5
Configuration Outputs C and D
and
Section 5.6.3 On-
board Circuits
for more details.
A2 Alarm Counter
This is a VdS 2540 requirement. The CIE can record a
maximum number of 9,999 alarm events. If this limit is
reached the alarm counter will automatically reset to zero.
It is not possible to reset the counter through the CIE,
except at access level 4.
A3 Fault Signals from Points
This is an optional VdS 2540 requirement. The CIE will
display fault signals from individual sensors and devices.