ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
52
997-457-000-8, Issue 8
January 2010
5.5.4.2 Number of Repeaters
The Number of Repeaters menu allows the quantity of
repeaters connected to the RS485 Communications Link
to be entered. The panel displays a fault if this quantity
does not equal the number of repeaters connected. To
enter the number:
1
From the Peripheral Options screen, press the ‘
1
’
button on the numeric keypad to select the RS485
Communications port option. The RS485 Protocol
setup screen is displayed:
2
Press the ‘
2
/
8
’ buttons to step through the
Peripheral Options until the Number of Repeaters
menu is displayed.
3
Press the ‘
6
’ button to enable the number or
repeaters to be entered.
4
Enter the required number using the numeric buttons;
for example if entering a value of 10, first press ‘1’,
then ‘0’.
5
Press the ‘
5
’ button to confirm the selection or press
‘
4
’ repeatedly to cancel and return to the Setup menu
screen.
5.5.4.3 RS485 Protocol
This option is used to select one of two available protocol
formats when repeaters are connected to the panel via
the RS485 communications link. The options available are:
a. NOTIFIER
b. ARP50/RP50.
The NOTIFIER protocol supports the IDR-2A and IDR-2P
Repeaters.
There are two additional options:
c. BFT/LLT repeater (Sweden only) communications link.
d. DISABLED - disables communication to any device
connected to the panel via the RS485 port.
1
or
8
2
6
[Setup]
RS485 Protocol =
NOTIFIER
> : Change
¦
: More
< : Exit
[Setup]
No. of Repeaters = 0
Enter new value 1 0
: Confirm
< : Cancel
[Setup]
No. of Repeaters = 0
Enter new value ____
: Confirm
< : Cancel
[Setup]
No. of Repeaters = 0
> : Change
¦
: More
< : Exit